MITSUBISHI ELECTRIC Changements pour le meilleur
France

Circuit breaker 4pole. Ir = 800 - 1600A; Icu / Ics = 85 / 43kA at AC 440V

FA-MCCB: Moulded-Case Circuit Breaker

SeriesWS SERIES - MCCB
TypeNF-S TYPE (STANDARD CLASS)
Frame Size1600
Rated Current (A)1600
Current TypeAC
Number of Poles4
Rated Voltage (V)690
Breaking Capacity at 400V (kA)85/43
Compliant with Standard(s)EN 60947-2, IEC 60947-2
Cycles with Rated Current500
Cycles without Rated Current3000
Automatic Tripping DeviceELECTRONIC

Dimensions et poids du produit

Depth (mm)190
Weight (kg)41,2
Width (mm)280
Height (mm)406

Conformity

CECOMPLIANT
Shipping ApprovalsNON-COMPLIANT
EACNON-COMPLIANT
UL/cULNON-COMPLIANT
UKCACOMPLIANT

Product Packaging

Aluminum (g)0
Others (g)0
Styrofoam (g)124
Cardboard (g)2071
Steel (g)10
Glass (g)0
Other plastic (g)0
Wood (g)0
Other paper (g)0

Environnement

REACH Limit ExceededNO
RoHS ComplianceCOMPLIANT
Dangerous Goods ClassNO
WEEEB2B
Dangerous Goods IdentifierNO